The question
How do loads travel through a steel structure to its foundations, and what keeps it stable?
Short answer
The Dubai Building Code requires a building to be stable, the features critical to its stability, including members that restrain critical members in compression, to be identified and included in the design, and continuous load paths to carry each action to the ground.1 For steel it adopts AISC 360,2 which requires stability of the whole structure and each element, allowing for second-order effects, imperfections, stiffness loss and deformations.3 Its direct analysis method uses second-order analysis, imperfections (usually represented by notional loads) and reduced stiffnesses.456 A brace that defines an unbraced length needs enough strength and stiffness to control member movement at the braced point; a user note points to Appendix 6 for methods, which do not apply to bracing that is part of the lateral force-resisting system.78 Part F also makes a robustness approach mandatory and requires construction-load assumptions on the drawings.910
How loads travel to the foundations
Part F asks for measures that keep the building stable under the design-basis loads and, where necessary, under the maximum credible loads for which the collapse limit state might be chosen as applicable.1 Every feature with a critical influence on overall stability has to be identified and included in the design, including all members that restrain critical members in compression.1 The structure has to provide continuous load paths that carry each action from its point of application to the ground.1
The Code’s Figure F.2, adapted from ACI 318-19 and drawn as a multi-storey concrete building, shows gravity and inertial loads, diaphragms with collectors, walls, a moment frame, an inclined column, a transfer slab and basement walls acting as one system.11
Practical consideration
A steel building has the same parts. Gravity load runs from the deck or slab through beams, girders, columns and base plates to the foundations. Wind load starts on the cladding; seismic load starts as the inertia of the masses, mostly at the floors and roof, as the figure’s in-plane and out-of-plane inertial loads show.11 Both reach the floor and roof planes (composite slabs, metal decks or plan bracing), and collectors carry them to braced bays, moment frames or cores and down through the bases, through a connection at every step.
- CladdingWind on the sheeting spans to the girts.
- Girts and wind postsThey carry it to the base and to eaves level.
- Roof planePlan bracing or a deck diaphragm carries it to the braced lines.
- Eaves strutsThey deliver it along each braced line.
- Vertical bracingBraced bays or portal frames take it to the bases.
- FoundationsBase plates, anchor rods and any shear key pass it into the ground.
Connections carry the path
AISC 360 designs connections to Chapters J and K, with forces and deformations consistent with the intended behaviour and the analysis.12 Beams, girders and trusses need restraint against rotation about their longitudinal axis at supports unless analysis shows otherwise.12 Simple connections may be modelled as pinned but need enough rotation capacity; fully restrained ones allow no relative rotation.12 Partially restrained connections need their force-deformation response in the analysis, and diaphragms and collectors are designed to Chapters C to K.13
Page F29 lists connection requirements: lifetime strength; stresses from restrained creep, shrinkage and temperature change; durability and fire resistance matching the connected elements; checks for all load scenarios, including horizontal earthquake and wind; and positive ties for precast members unless seating exceeds the maximum expected movement.14 The list continues F.6.4.6 on precast concrete connections, not the steel clause F.6.5 printed beside it.152
Practical consideration
They are good questions for any steel connection, but cite them as precast provisions; item e) applies directly where precast planks or stairs sit on steel beams.
Bolted steel connections follow the AISC steel construction manual and the specification for structural joints using ASTM A325 or A490 bolts; welding follows AWS D1.1 or BS EN ISO 15614.16 Site welding should not be undertaken; if it is unavoidable, a method of work with certificates and tests must be submitted for approval for approval and accredited welders are used.16 No connection may rely on welds and bolts acting together.16
Structures resist self-straining forces from expansion and contraction, and relieving details may be used where practical if they do not break an assumed load path.17 For steel members and members exposed to the sun, a range equal to the maximum temperature swing is appropriate; ±25 °C may be used for protected steel, and exposed steelwork is assessed case by case.17
Practical consideration
A slotted hole or sliding bearing that releases thermal movement cannot also be the only route for a bracing force in that direction.
What keeps a steel frame stable
AISC 360 requires the structure and its elements to be designed for stability to Chapter C.13 Stability is required of the whole structure and of every element, taking account of member and connection deformations, second-order P-Δ and P-δ effects, geometric imperfections, stiffness loss from partial yielding and residual stresses, and uncertainty in strength and stiffness.3 They are calculated at LRFD or 1.6 times ASD combinations, and any rational method covering all of them is permitted.3
Practical consideration
P-Δ is the extra moment from gravity load on a swayed storey; P-δ, from axial load on a member bowed between its ends. Sway is resisted by braced frames, moment frames, portal frames, fixed-base columns or cores. The remaining columns carry gravity only and lean on those systems, so their load belongs in the stability analysis;18 in a portal-framed shed, every column may be part of the lateral system in the frame direction.
When a frame or a member needs bracing
Under the direct analysis method, flexural buckling is checked on the unbraced length unless rational analysis justifies less, and bracing that defines an unbraced length must have enough stiffness and strength to control movement at the braced points.7 A user note points to Appendix 6, which does not apply to bracing in the lateral force-resisting system.7 Appendix 6 gives the minimum strength and stiffness to create a braced point in a column, beam or beam-column.8
A beam has to be restrained against twist at its supports. Between supports, a braced point needs lateral or torsional bracing, or both, to stop relative movement of the flanges; an inflection point is a braced point only if braced.19 Lateral bracing goes at or near the compression flange, except at a cantilever’s free end (top flange) and at the brace nearest an inflection point in double curvature (both flanges).19 These rules cover doubly and singly symmetric I-shaped members bent in a plane of symmetry with zero net axial force.19 Torsional bracing may be attached anywhere on the section; a user note gives cross-frames, moment-connected beams and vertical diaphragms as point braces, and slabs or decks as continuous bracing.20
The effective length method of Appendix 7 is the alternative. In braced-frame and shear-wall systems it takes K = 1.0 unless a smaller value is justified; in moment frames, K or the buckling stress of the columns that provide lateral stiffness comes from a sidesway buckling analysis, and other columns take K = 1.0; an exception permits K = 1.0 for all columns where the second-order to first-order drift ratio, for LRFD or 1.6 × ASD combinations, is 1.1 or less in every storey.21
Practical consideration
Do not mix the two: K factors belong to the effective length method; the direct analysis method designs members on their unbraced length.
Practical consideration
A steel frame needs bracing in three senses: a lateral system in each principal direction, tied to every floor and roof by diaphragms; member bracing wherever the design relies on an unbraced length shorter than the member; and temporary bracing during erection. A portal rafter carries axial force as well as bending, and its compression flange changes sides near the haunches and under wind uplift, so its purlin and fly-brace restraints are beam-column bracing under 6.4;22 channel and Z sections fall outside the I-shape scope of 6.3.19 Seismic systems also follow AISC 341, which the Code requires and this library does not hold.2
Designing for stability: the direct analysis method
The direct analysis method is permitted for all structures; with elastic analysis, required strengths come from C2 and available strengths from C3.3 Members and connections are then checked to Chapters D to K with no further check of overall stability.7
The analysis includes all deformations that contribute to displacement, uses the C2.3 reduced stiffnesses, and is second-order, covering P-Δ and P-δ.4 P-δ may be left out of the overall response only when gravity is carried mainly by nominally vertical members, the ratio of maximum second-order to first-order drift, for LRFD or 1.6 × ASD combinations with C2.3 reduced stiffness, is 1.7 or less in every storey, and moment-frame columns carry no more than one-third of the gravity load in the direction considered; members in compression and bending still include P-δ.4 Appendix 8’s approximate method is permitted, and all loads that influence stability are included,4 including, a user note says, leaning-column loads.18 ASD analyses run at 1.6 times the ASD combinations, with results divided by 1.6.18
System imperfections, chiefly column out-of-plumbness, are either modelled directly, which is always permitted, at the largest amount considered and in the most destabilising pattern, or represented by notional loads.18 Notional loads may be used where gravity is carried mainly by nominally vertical members: lateral loads at every level, added to the other lateral loads in all combinations except as C2.2b(d) allows, of Ni = 0.002 α Yi (Eq. C2-1), with α = 1.0 for LRFD and 1.6 for ASD and Yi the gravity load at level i, spread like that load in the most destabilising direction.5 A user note adds that the fictitious base shear can be corrected at the base, but the extra overturning is real.5 Another says that for most buildings two orthogonal directions, each in both senses and in the same direction at all levels, satisfy the direction rule in gravity-only combinations, and the resultant lateral-load direction otherwise.6
The 0.002 coefficient reflects an out-of-plumbness of 1/500 and may be scaled for a different justified maximum; a user note identifies 1/500 as the Code of Standard Practice column tolerance and warns that tolerances on the plan position of columns can require tighter plumbness.6 Where gravity is carried mainly by nominally vertical members and the drift ratio, for LRFD or 1.6 × ASD combinations with C2.3 reduced stiffness, is 1.7 or less in every storey, modelled imperfections and notional loads may both be confined to gravity-only combinations.56
Stiffnesses that contribute to stability are factored by 0.80, which may be applied to all stiffnesses, and the flexural stiffness of members contributing to stability by a further τb.6 For noncomposite members τb = 1.0 when αPr/Pns is 0.5 or less (Eq. C2-2a), otherwise τb = 4(αPr/Pns)[1 − (αPr/Pns)] (Eq. C2-2b), with Pns = FyAg for nonslender sections.7 Where C2.2b applies, τb = 1.0 may be used for all noncomposite members if an extra 0.001 α Yi is applied at all levels, in the C2.2b(b) direction, in all combinations and whatever the drift ratio.7 Non-steel components take any larger reductions their own codes require.7
Practical consideration
The Code allows only analysis and design software approved by the Authority.23 In it, check that second-order analysis is on, that the 0.8 and τb reductions are in the strength model (C2.3 applies them to the analysis for required strengths)6 and that notional load cases are in the combinations. Use nominal stiffness for serviceability drift.
| Step | Value | Basis |
|---|---|---|
| Building | Two storeys of 4.5 m; gravity on columns, lateral load on braced bays | Assumed |
| Gravity per level, LRFD | Y1 = 6000 kN at the first floor; Y2 = 3500 kN at the roof | Assumed |
| Notional loads (α = 1.0) | N1 = 0.002 × 1.0 × 6000 = 12.0 kN; N2 = 0.002 × 1.0 × 3500 = 7.0 kN | Eq. C2-1 |
| Base shear correction | Equal and opposite 12.0 + 7.0 = 19.0 kN at the base | C2.2b user note |
| Overturning (real) | 12.0 × 4.5 + 7.0 × 9.0 = 54.0 + 63.0 = 117.0 kNm | C2.2b user note |
| τb = 1.0 alternative | Add 0.001 × 6000 = 6.0 kN and 0.001 × 3500 = 3.5 kN in all combinations | C2.3(c) |
| τb calculated | αPr/Pns = 0.6: τb = 4 × 0.6 × (1 − 0.6) = 0.96; flexural stiffness 0.8 × 0.96 = 0.768 EI | Eq. C2-2b; C2.3(a) |
| Plumbness tolerance of 1/400 | Coefficient 0.002 × 500/400 = 0.0025; N1 = 0.0025 × 6000 = 15.0 kN | C2.2b(c) |
| ASD (α = 1.6) | Y1 = 4400 kN: N1 = 0.002 × 1.6 × 4400 = 14.08 kN, analysed at 1.6 times the ASD combination | Eq. C2-1; C2.1(d) |
Illustrative loads; in a real design each Yi comes from the project’s load combinations.5 The τb rows apply only to members whose flexural stiffness contributes to stability.67 ASD results are divided by 1.6.18 Arithmetic checked by an independent recalculation. Illustration only.
When the effective length or first-order method may be used
Chapter C also permits two elastic alternatives in Appendix 7, the effective length method and the first-order analysis method, within that appendix’s limits.4 The C1 requirements still apply to both.24
The effective length method needs gravity carried mainly by nominally vertical columns, walls or frames and a ratio of maximum second-order to first-order drift, for LRFD or 1.6 × ASD combinations, of 1.5 or less in every storey, with stiffness not reduced under C2.3; a user note allows the ratio to be taken as B2 from Appendix 8.24 Its analysis uses nominal stiffness and C2.2b notional loads.24 A user note says those loads are needed only in gravity-only combinations, and an exception in 7.2.3 permits K = 1.0 for every column where that drift ratio, on the same basis, is 1.1 or less in every storey.21
The first-order analysis method needs the same gravity condition, the same 1.5 limit with unreduced stiffness, and αPr no greater than 0.5Pns (Eq. A-7-1) in every member whose bending stiffness contributes to lateral stability.25 Every combination then includes an extra lateral load at each level of Ni = 2.1 α (Δ/L) Yi, at least 0.0042 Yi (Eq. A-7-2), where Δ/L is the largest first-order storey drift ratio, spread like the gravity load in the most destabilising direction.25 Member moments are amplified by B1, and flexural buckling uses the unbraced length unless a smaller value is justified by rational analysis.26
Sizing a stability brace: AISC 360 Appendix 6
One bracing system serving several members is designed for the sum of their required strengths, and the stiffness it provides includes its connections and anchoring details.8 A user note distinguishes panel bracing, which limits relative sideways movement between braced points, point bracing, which controls movement at its own point, and continuous bracing.8 Brace members and connections must provide the required strength and stiffness unless analysis justifies less, and braced members may then use Lc and Lb equal to the distance between braced points.8
Alternatively, the brace strength and stiffness may come from a second-order analysis that satisfies Chapter C or Appendix 1, with the brace points displaced in the most demanding pattern; or the stiffness may be taken as 2/φ (LRFD) or 2Ω (ASD) times the ideal stiffness from a buckling analysis, with the brace strength still taken from 6.2 to 6.4. Either route allows Lc and Lb shorter than the distance between braced points.27
Column bracing is assumed to act at the shear centre; a user note warns that bracing that does not prevent twist leaves the column open to torsional buckling under E4.27 Panel bracing needs Vbr = 0.005Pr (Eq. A-6-1) and βbr = (1/φ)(2Pr/Lbr) for LRFD or Ω(2Pr/Lbr) for ASD (Eq. A-6-2a and b),28 and its connection to the column needs the strength of a point brace.27 Point bracing needs Pbr = 0.01Pr (Eq. A-6-3) and βbr = (1/φ)(8Pr/Lbr) or Ω(8Pr/Lbr) (Eq. A-6-4a and b), with φ = 0.75 and Ω = 2.00.28 Pr is the largest required axial strength either side of the brace, the larger Pr/Lbr sets the stiffness, and for intermediate point bracing of an individual column Lbr need not be taken below the longest effective length at which the column still carries Pr.28
For I-shaped beams, panel bracing needs Vbr = 0.01(MrCd/ho) (Eq. A-6-5) and βbr = (1/φ)(4MrCd/(Lbr ho)), with Ω in place of 1/φ for ASD (Eq. A-6-6a and b).19 Point bracing needs Pbr = 0.02(MrCd/ho) (Eq. A-6-7) and βbr = (1/φ)(10MrCd/(Lbr ho)), likewise (Eq. A-6-8a and b), with φ = 0.75 and Ω = 2.00; ho is the distance between flange centroids, and Cd is 1.0, or 2.0 for the brace nearest the inflection point in double curvature.20
A torsional point brace needs Mbr = 0.02Mr (Eq. A-6-9) and a stiffness combining the brace system requirement with the web’s distortional stiffness (Eq. A-6-10 to A-6-12), with φ = 0.75 or Ω = 3.00.29 A user note warns that a web with too little distortional stiffness makes the torsional bracing ineffective.22 For continuous torsional bracing such as a deck, the strength per unit length is Eq. A-6-9, with Mr the maximum throughout the span, divided by the maximum unbraced length permitted under Mr, and the stiffness uses Eq. A-6-10 and A-6-11 with L/n = 1.0 and Eq. A-6-13.22
For a beam-column, the axial and flexural requirements are added, panel with panel and point with point, using the actual unbraced length without the minimum-length relaxations.2230 Where axial force and bending together put both flanges into compression, both flanges have to be restrained.30
| Step | Value | Basis |
|---|---|---|
| Arrangement | 8.0 m pinned column braced about its weak axis at mid-height by a 6.0 m strut to a braced-bay node; Pr = 1500 kN (LRFD), 1050 kN (ASD); Lbr = 8000/2 = 4000 mm | Assumed; App. 6.2.2 |
| Brace demand, LRFD | Pbr = 0.01 × 1500 = 15.0 kN; βbr = (8 × 1500/4000)/0.75 = 4.0 kN/mm | Eq. A-6-3, A-6-4a |
| Brace demand, ASD | Pbr = 0.01 × 1050 = 10.5 kN; βbr = 2.00 × 8 × 1050/4000 = 4.2 kN/mm | Eq. A-6-3, A-6-4b |
| Trial strut | Idealised round tube, D = 88.9 mm, design wall t = 4.0 mm, Fy = 250 MPa: A = 1066.9 mm², r = 30.05 mm, D/t = 22.2 below 0.11E/Fy = 88; EA/L = 200 × 1066.9/6000 = 35.6 kN/mm | B4.2; Table B4.1a case 9; App. 6.1 |
| Strut compression | Lc/r = 6000/30.05 = 199.7, above 4.71√(E/Fy) = 133.2; Fe = π² × 200 000/199.7² = 49.5 MPa; Fcr = 0.877 × 49.5 = 43.4 MPa; Pn = 43.4 × 1066.9 = 46.3 kN | E2 user note; Eq. E3-4, E3-3, E3-1 |
| One column | φcPn = 0.90 × 46.3 = 41.7 kN ≥ 15.0 kN; Pn/Ωc = 46.3/1.67 = 27.7 kN ≥ 10.5 kN: passes | E1 |
| Four columns on one strut line | ΣPr = 4 × 1500 = 6000 kN: Pbr = 0.01 × 6000 = 60.0 kN; βbr = (8 × 6000/4000)/0.75 = 16.0 kN/mm, needing A ≥ 16.0 × 6000/200 = 480 mm²; 41.7 kN is below 60.0 kN, so the trial strut fails | App. 6.1 |
| Four columns: area needed | At Lc/r = 200, Fcr = 0.877 × 49.35 = 43.28 MPa and φcFcr = 38.95 MPa, so A ≥ 60 000/38.95 = 1540 mm² | Eq. E3-3, E3-4 |
| Four columns: larger tube | D = 114.3 mm, t = 4.0 mm: A = 1386.1 mm², r = 39.02 mm, Lc/r = 153.8, Fcr = 0.877 × 83.5 = 73.2 MPa, Pn = 73.2 × 1386.1 = 101.5 kN, φcPn = 91.3 kN ≥ 60.0 kN; EA/L = 46.2 kN/mm ≥ 16.0 kN/mm | Eq. E3-1 to E3-4 |
The brace acts at the shear centre and the column is otherwise restrained against twist;27 the actual 4000 mm for Lbr is conservative.28 φc = 0.90 and Ωc = 1.67;31 above 4.71√(E/Fy), Eq. E3-3 applies32 with Fe from Eq. E3-4,33 so Fcr does not depend on the assumed Fy. The wall is nonslender under Table B4.1a case 9,34 and t is the design thickness, 0.93 times nominal for HSS made to standards other than ASTM A1065 or A1085.35 Self-weight, eccentricity and connection and bay flexibility are excluded. Arithmetic checked by an independent recalculation. Illustration only.
Practical consideration
Connection and anchorage stiffness count in what the brace provides;8 in our reading, the brace force must therefore reach something stiff at its far end, such as a braced bay, diaphragm or wall. Bolts in oversized or slotted holes can slip before they bear, so the connection can limit the stiffness. As the example shows, neither the slenderness preference nor the stiffness requirement sizes a strut on its own; check its compression strength against Pbr as well.
Robustness and structural integrity
Part F makes robustness against disproportionate collapse mandatory by one of two approaches: direct design, which checks progressive collapse explicitly by the tie-force, alternate-path or enhanced-local-resistance method, with details in UFC 4-023-03; or indirect design, which provides minimum levels of strength, continuity and ductility.9 It recommends direct design, and Table F.2 links the checks to risk category: nothing specific for category I; the indirect approach or either of two direct options for II; and combinations of alternate-path and enhanced-local-resistance checks for III and IV, with tie forces added for IV.9
Where the building code requires structural integrity design, AISC 360 B3.9 sets minimum nominal tensile strengths: column splices at least D + L for the tributary area between that splice and the next splice or base beneath; beam and girder end connections two-thirds of the required vertical shear (LRFD) or the full required shear (ASD), and not less than 10 kips, a value printed without an SI equivalent.13 That is about 44.5 kN (our conversion). End connections of members bracing columns need 1% of two-thirds of the column’s required axial strength at that level (LRFD), or 1% of that strength (ASD).36 These checks stand apart from other strength checks and permit bearing bolts in short-slotted holes parallel to the force and inelastic connection deformation.36
Practical consideration
Because one F.5.5 approach is mandatory,9 the basis of design should say which is used and how it is met. No Code clause we found calls up B3.9 for steel, but for the indirect approach its connection tensions are a practical way to show minimum strength and continuity; if they are not used, justify the alternative.
Stability during construction
The design has to allow for safe fabrication, transport, handling and erection.23 Minimum construction loads follow ASCE 37, which is not held here.10 The Engineer includes construction-stage loads, including stresses locked in by the sequence, states the construction-load assumptions on the detailed design drawings, verifies every stage; any departure from those assumptions by the Contractor’s construction sequence has to be assessed.10
AISC 360 requires column bases to be set level with full bearing and the frame to be carried up true and plumb within the Code of Standard Practice limits.37 As erection proceeds the structure has to be secured for the loads expected, with temporary bracing left in place as long as safety requires.37
Part F requires drift and deformation to be assessed over the structure’s whole life, including construction,38 with deviation from plumb under permanent gravity load verified against Section 7 of ACI 117-10, which is not held here.38 Differential vertical shortening should be assessed by a nonlinear static construction-sequence analysis, which the Engineer and/or Contractor has to perform, at a minimum, for multi-storey buildings with different core and perimeter stresses, asymmetric plans or massing, stepped setbacks or outriggers.38
Practical consideration
The permanent stability system is often completed last, so show which bays are erected and braced first, which members must not be removed and when temporary bracing may come out. Specify a frame plumbness tolerance no looser than the out-of-plumbness assumed in the analysis, or scale the notional loads.6
Drift limits for the lateral system
Wind drift is assessed under F.7.12.4, and seismic movement under Section 12.12 of ASCE/SEI 7-16, which is not held here.38 F.7.12.4 sets overall and inter-storey displacement limits under 10-year return wind pressures in Table F.11;39 the serviceability guide gives the values and discusses the clause’s wording.
Practical consideration
Keep the drift ratios apart. Table F.11 is a serviceability check under 10-year wind. The AISC ratios compare second-order with first-order drift at strength-level combinations: the 1.7 limit of C2 uses the C2.3 reduced stiffness,4 the 1.5 limit of Appendix 7 uses unreduced stiffness,24 and the 1.1 limit that allows K = 1.0 belongs to the effective length method.21
What to record in the design basis
The Code requires the features critical to stability to be identified and included in the design,1 the construction-load assumptions to be stated on the detailed design drawings,10 one robustness approach to be used,9 and analysis and design software approved by the Authority to be used.23
Practical consideration
AISC 360 leaves the stability method to the designer within limits,4 so record which is used and why, with the software’s name, version and stability settings. We also recommend showing restraint members, released connections and the erection concept on the drawings.
| Item | Example entry | Basis |
|---|---|---|
| Load paths and lateral system | Paths traced in both directions; braced bays on stated grid lines; floor slab and roof plan bracing with collectors | F.5.4; AISC B3.5 |
| Stability method | Direct analysis; P-Δ with B1 only where gravity is carried primarily by nominally vertical members, the reduced-stiffness drift ratio (LRFD or 1.6 × ASD) is 1.7 or less and moment-frame columns carry at most one-third of the gravity load | AISC C1.1, C2.1 |
| Imperfections and stiffness | Notional loads 0.002αYi (1/500) matched by the erection tolerance; 0.8 and τb, or τb = 1.0 with 0.001αYi | AISC C2.2b, C2.3 |
| Member bracing | Struts and beam restraints to Appendix 6, with strut compression; rafter restraints as beam-column bracing | F.5.4; AISC Appendix 6, E3 |
| Robustness | F.5.5 approach and how it is met, for example B3.9 connection tensions for the indirect approach | F.5.5; AISC B3.9 |
| Construction stage | Erection sequence, temporary bracing, construction loads on the drawings | F.7.7; AISC M4.2 |
| Software | Software approved by the Authority; name, version and stability settings | F.5.1; settings are our recommendation |
Our example, not an Authority template. The load-path and restraint entries answer F.5.41 and the software entry F.5.1;23 the analysis method and its settings are choices AISC 360 lets the designer make and justify.4
Load-path and stability checklist
- Every load traced to the foundations in both directions, each floor and roof tied into the lateral system
- Members restraining critical compression members identified and included in the design
- Stability method named, with the drift ratio and stiffness basis that permit it
- Second-order analysis, leaning-column loads, notional loads, 0.8 and τb in the strength model
- Brace strength, stiffness and compression capacity checked, summed where one line braces several members
- Construction-load assumptions on the drawings; temporary bracing until the permanent system is complete
- Robustness approach recorded, with how it is met
- Released connections do not break a load path
A working list for a junior engineer. It is not an approval checklist.
Scope and limits
Practical consideration
This guide reads the 2021 Dubai Building Code and ANSI/AISC 360-16 as checked on the date shown; the Code names AISC 360 without an edition, and later amendments and circulars were not audited. Named but not held: ASCE/SEI 7-16, ASCE 37, ACI 117-10, ACI 318-19, UFC 4-023-03, AISC 341, the AISC Code of Standard Practice, Commentary and steel construction manual, and BS EN ISO 15614. AWS D1.1:2020 and a 2025 structural-joints specification are held but were not read here. No held source covers deck or sheeting diaphragm design. Seismic systems are out of scope. This guide is not a design; review and acceptance sit with the project’s appointed engineer and the Authority.
Questions this guide answers
Source notes
Numbered notes point to the exact section and physical PDF page. Page numbers are the PDF viewer’s page, which can differ from the number printed on the page. Sources checked 25 September 2026. These notes support the statements; they are not a substitute for reading the current document for a project.
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.5.4 Structural stability (printed page F13), PDF page 339. Open the publisher PDF at page 339 (opens in a new tab) ↩ ↩ ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.6.5.1 Design basis and F.6.5.2 Steel grades, right-hand column (printed page F29), PDF page 355. Open the publisher PDF at page 355 (opens in a new tab) ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Chapter C introduction, C1 General stability requirements and C1.1 Direct analysis method, printed page 16.1-22. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Sections C1.2 Alternative methods, C2 and C2.1(a)-(c) General analysis requirements, printed page 16.1-23. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section C2.2a continued and C2.2b(a)-(b) Use of notional loads, Eq. C2-1, printed page 16.1-25. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section C2.2b User Notes, C2.2b(c)-(d) and C2.3(a)-(b) Adjustments to stiffness, printed page 16.1-26. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section C2.3(b)-(d), Eq. C2-2a and C2-2b, and C3 Calculation of available strengths, printed page 16.1-27. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6 introduction, User Note and 6.1 General provisions, printed page 16.1-237. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.5.5 Robustness against disproportionate collapse and Table F.2 (printed page F15), PDF page 341. Open the publisher PDF at page 341 (opens in a new tab) ↩ ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.7.7 Construction load (printed page F35), PDF page 361. Open the publisher PDF at page 361 (opens in a new tab) ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, Figure F.2 Typical actions and structural system and its key (printed page F14), PDF page 340. Open the publisher PDF at page 340 (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section B3.4 Design of connections and supports, B3.4a Simple connections and B3.4b(a) FR moment connections, printed page 16.1-13. Publisher page (opens in a new tab) ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Sections B3.4b(b) PR moment connections, B3.5 Diaphragms and collectors, B3.7 Design for stability and B3.9(a)-(b) Structural integrity, printed page 16.1-14. Publisher page (opens in a new tab) ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.6.4.6 continued: connection requirements a) to e), left-hand column above F.6.4.7 Precast staircase (printed page F29), PDF page 355. Open the publisher PDF at page 355 (opens in a new tab) ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.6.4.6 Connections (precast concrete), right-hand column (printed page F28), PDF page 354. Open the publisher PDF at page 354 (opens in a new tab) ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.6.5.4.1 Bolted connections and F.6.5.4.2 Welded connections (printed page F31), PDF page 357. Open the publisher PDF at page 357 (opens in a new tab) ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.7.10 Self-straining forces and F.7.11 Thermally induced forces (printed page F35), PDF page 361. Open the publisher PDF at page 361 (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section C2.1(c) User Note, C2.1(d), C2.2 and C2.2a Direct modeling of imperfections, printed page 16.1-24. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.3 Beam bracing, 6.3.1 Lateral bracing and 6.3.1a Panel bracing, Eq. A-6-5 and A-6-6, printed page 16.1-240. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.3.1a symbols, 6.3.1b Point bracing, Eq. A-6-7 and A-6-8, and 6.3.2 Torsional bracing, printed page 16.1-241. Publisher page (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 7.2.2 User Note, 7.2.3 Available strengths and exception, printed page 16.1-246. Publisher page (opens in a new tab) ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.3.2a User Notes, 6.3.2b Continuous bracing, Eq. A-6-13, and 6.4(a) Beam-column bracing, printed page 16.1-243. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.5.1 General conditions (printed page F12), PDF page 338. Open the publisher PDF at page 338 (opens in a new tab) ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 7 introduction, 7.1 General stability requirements, 7.2.1 Limitations and 7.2.2 Required strengths, printed page 16.1-245. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 7.3.1(a)-(c) Limitations, Eq. A-7-1, and 7.3.2(a) Required strengths, Eq. A-7-2, printed page 16.1-247. Publisher page (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 7.3.2(b) and 7.3.3 Available strengths, printed page 16.1-248. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.1(a)-(c), 6.2 Column bracing and 6.2.1 Panel bracing, printed page 16.1-238. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.2.1 Eq. A-6-1 and A-6-2, and 6.2.2 Point bracing, Eq. A-6-3 and A-6-4, printed page 16.1-239. Publisher page (opens in a new tab) ↩ ↩ ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.3.2a Torsional point bracing, Eq. A-6-9 to A-6-12, printed page 16.1-242. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Appendix 6.4(b)-(d) Beam-column bracing, printed page 16.1-244. Publisher page (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Chapter E, E1 General provisions, printed page 16.1-33. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Sections E2 Effective length, with User Note on Lc/r, and E3, Eq. E3-1 to E3-3, printed page 16.1-35. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section E3, Eq. E3-4, printed page 16.1-36. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Table B4.1a, case 9 Round HSS, printed page 16.1-17. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section B4.2 Design wall thickness for HSS, printed page 16.1-20. Publisher page (opens in a new tab) ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section B3.9(c) and closing paragraph on structural integrity, printed page 16.1-15. Publisher page (opens in a new tab) ↩ ↩
Specification for Structural Steel Buildings (ANSI/AISC 360-16), ANSI/AISC 360-16, July 7, 2016. American Institute of Steel Construction (AISC). Section M4.1 Column base setting and M4.2 Stability and connections, printed page 16.1-171. Publisher page (opens in a new tab) ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.8.6 Drift and deformation of buildings, F.8.6.1 to F.8.6.5 (printed page F46), PDF page 372. Open the publisher PDF at page 372 (opens in a new tab) ↩ ↩ ↩ ↩
Dubai Building Code, 2021 Edition. Government of Dubai; official copy hosted by Dubai Development Authority. Part F, F.7.12.4.1 Allowable displacement and Table F.11 Displacement limits (printed page F38), PDF page 364. Open the publisher PDF at page 364 (opens in a new tab) ↩